ioLogik 4000 I/O 連網伺服器
乙太網路I/O資料讀取與控制解決方案
More Info
 
 

薄片式I/O模組結合的全範圍I/O模組架構

 

Automatic search for installed ioLogik servers
ioAdmin can automatically search for installed ioLogik servers. The
automatic search function supports both Ethernet and RS-232/485
searching.

 

 

 


Online Documentation
Traditionally, engineers needed to manually prepare a wiring handbook. ioAdmin provides convenient online documentation that engineers may use when planning or troubleshooting field wiring. The online documentation not only covers module types, but also includes a wiring guide. The search by keyword function gives engineers a more efficient means of reducing overall installation time.

 



Report Generation

To help you record I/O module combinations and parameters, ioAdmin can generate a report file in text format that may be used to help manage the system. There are three areas in the report. One is for slice models, another is for slice configurations, and the third is for the Modbus address table. To help you configure SCADA, you can see the combination of slices in the slice models and the Modbus address in the Modbus address table. This is particularly helpful since the Modbus address is dynamically dependent on the combination of slices.


Remote Configuration
ioAdmin is a powerful, Windows-based configuration and management tool. You may use ioAdmin to modify the IP address, update communication parameters, and configure all other settings easily. In addition, ioAdmin can be used to configure ioLogik I/O servers from a remote host. This means that ioLogik servers may be configured from anywhere over the Ethernet, which may help reduce operating costs.


I/O Testing
ioAdmin provides a test function to verify reliable operation of digital and analog output channels. Traditionally, users needed to use a meter to check the status of each sensor. With ioLogik servers, they may use ioAdmin’s intuitive software interface to test digital and analog output channels. Digital output: Use the switch to test the on/off status. Analog output: Use the slider to test the voltage output.

 


Safe Status with Communication Watchdog Timer

ioLogik 4000 servers are equipped with a builtin watchdog timer that monitors the Modbus communication status. If Modbus communication between the remote I/O server and a host computer or a PLC is interrupted for a user-defined period of time, the watchdog can activate safe status to reset all output channels to a user-defined state. The watchdog ensures the safety of field operations when communication is a problem.

Digital output channels may be set to On, Off, or Hold Last Status when safe status is activated. Analog output channels may be set to Fixed Safe Value, Low Limit, or High Limit when safe status is activated. For example, if you predefine the safe status of the DO to “off,” when the Modbus communication times out, the safe status will change the DO status to “off.”


Self-Diagnostic Function for Digital Output Channels

The M-2402/2403/2404/2405 modules provide a self-diagnostic function to guarantee that the digital output signal is monitored electronically. The hardware-monitored status will write back to the logic system. After the software sends a command to the above I/O models, you will get the actual digital out status over the network. This is all done internally; configuration is not required.


Check Remote I/O Status with a Web Browser

ioAdmin is the main configuration interface for ioLogik servers. However, you can also check some information using the ioLogik server’s web console. The following information can be obtained using your web browser:
• Network configuration
• Expansion module
• Status of each channel



Supports Various SCADA Software Packages
The ioLogik 4000 line was designed using the standard Modbus protocol and can be used with most SCADA systems. The following SCADA software was found to be compatible with ioLogik 4000 servers: Modicon Driver, Wonderware Intouch, GE Fanuc iFix and CIMPLICITY, Broadwin,kingview, and Citect. In addition, we successfully tested OPC Server “Kepware,” which means that ioLogik 4000 servers may be accessed using SCADA or OPC Server. (Note: You can download the installation guide for different SCADA software packages from Moxa’s
download center)